Permit: T07CM04788

Parcel: 105110700


Addresses:

4370 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04788

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119 ALSO, IDENTIFY FOR ISOLATED GROUND
2. SEAL WALK-IN BOXES AS PER 300.7 (H2 8/25/08)
3. PANEL DIRECTORIES TO BE AS PER 408.4 -
NO ABBREVIATION (#5 8/25/08)

PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION
08/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT RACEWAY DROPS BOTH ENDS
2. TIGHTEN LOOSE FITTINGS
3. FINISH PREVIOUS ITEMS 1, 2, 5 AND 8

ROOF:
1. TIGHTEN ALL LOOSE FITTINGS
2. RECEPTACLE COVER - 406.8
08/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION - CK ROOF AND FINISH NEXT TIME

1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
OR 1/8" AROUND BOX 314.21
2. SEAL WALK IN BOX PER 300.7
3. FINISH SWITCH BY WALK IN, GONDOLA LIGHTS
4. USE TERMINAL ENDS WITH STRANDED CONDUCTORS AT SCREWS
5. CIRCUIT DIRECTORIES AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
6. MAINTAIN WORKING CLEARANCES AT DISCONNECTS
7. BOND ACROSS CONCENTRICS 250.97
8. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
9. VERIFY LISTING FOR HUMIDIFIER
10. DISCONNECT NEEDED FOR A/C UNIT IN CIGAR BOX
08/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK HIGH BAY AND TRACK LIGHTS

DISCUSSED BARRIER AT PANELS