Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04782
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIR LOOSE RECEPTACLE NORTHEAST CORNER INSIDE STORE 2. ROMEX NOT APPROVED WIRING METHOD FOR ABOVE GRID LIGHT FIXTURES ETC. 334.12 NEC 3. EXPOSED WIRING EAST ROOM ABOVE CEILING 4. SIGN IN FRONT IS ABANDON AT J-BOX INSIDE BLD. 5. CALL BEE EXTERMINATOR PRIOR TO NEXT INSPECTION BEE HIVE IN FRONT OF ELEC. SERVICE 6. OK ROOF 7. ISOLATE NEUTRAL AND GROUNDS AT SUB-PANEL 8. SEE NOTE #6 LAST INSPECTION, A REINSPECTION FEE WILL BE ASSESSED IF NO COMPLIANCE |
|
05/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED WIRING AND SPLICES IN FRONT & BACK OF UNIT 2) MISSING DEAD FRONT AT SERVICE PANEL WIRING NOT TO CODE, UNSUPPORTED CONDUITS 3) PROVIDE LADDER FOR ROOF INSPECTION AND INSIDE CEILING, IT APPEARS WORK (ELECTRICAL) WAS DONE WITHOUT PERMITS AND INSPECTIONS 4) DISPLAY COUNTERS NOT WIRED PER CODE 5) SIGN IN FRONT NOT TO CODE 6) OBTAIN THE SERVICES OF A LICENSED OR QUALIFIED ELECTRICIAN TO MAKE REPAIRS AND RECALL INSPECTION |