Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM04768

Parcel: 13314456A


Addresses:

1111 N EL DORADO PL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/06/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/05/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
704-4-5
"FASTENERS SHALL BE OF BRASS OR EQUALLY (STAINLESS) CORROSION RESISTANT MATERIALS"
05/02/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLOOR LINER OK
NEED TO SEE CLOSET FLANGE INSTALLATION
04/17/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FLOORS IN TR'S SHALL SLOPE TOWARD FD AND SHALL BE MADE WATER TIGHT. RED GUARD INSTALLATION REQUIREMENTS SPECIFIY FIBERGLASS MESH BETWEEN FD CLAMPING RIING AND EXTENDING OUT 1' FOOT
04/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- LETTER FROM M&C RECEIVED FOR MCU AND
FLOOR OUTLET WCS
P-4 MS DWV OK TO COVER
03/31/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER PIPING OK
WATER HEATERS IN RESTROOMS OK
SHALL SEE TEST OF FLOOR DRAIN FOR WATERPROOF AND CORRECT CLOSET FLANGE INSTALL
03/27/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PRE-SLAB OK IF FLOOR MOUNTED CARRIERS ARE ALLOWED
DWV TEST THRU ROOF OK
03/21/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- JOB OFFICE IS LOCATED IN BUILDING 1161 UNIT 339
- WYE PATTERN FITTINGS ON CO'S OR CAP UPPER LEVEL
LAV CO'S
- SWEEPS REQUIRED ON TRAP ARMS
- TYPE L COPPER SPECIFIED
- REAM ALL JOINTS
- WATER HAMMER ARRESTORS REQUIRED ON FLUSH O METERS BRANCHES
- PROVIDE PROPER WH DRAIN PAN DRAINS
- CHAIR CARRIERS AND URINAL CARRIERS SPECIFIED ON FIXTURE SCHEDULE.