Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS BATHROOMS ONLY SUBJECT TO BUILDING INSPECTORS APPROVAL |
|
| 03/31/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE ENGINEER VERIFY USAGE OF MC CABLE AND SET SCREW FITTINGS 2. SUPPORT FIRE ALARM CABLE PER 760 3. SUPPORT EMT WITHIN 3' OF BOXES 4. HAVE BUILDING INSPECTOR CHECK FIRE STOPPING BETWEEN FLOORS 5. MISSING KO SEAL - FILL UNUSED OPENINGS IN BOXES ALSO COVERS 6. BROKEN FLEX TO WATER HEATER |
|
| 03/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ONE ON SITE NO PLANS ON SITE NO NUMBER TO CALL |