Permit: T07CM04760

Parcel: 128100810

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM04760

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
TESTED DUCT SMOKE DETECTOR
05/06/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
05/01/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- SUPPORT REFER LINES ON ROOF
- CONDENSORS NOT FUSED CORRECTLY
- PROVIDE REDWOOD SLEEPERS UNDER CONDENSORS AND SECURD
- PAINT EXPOSED PVC ON ROOF
- PROVIDE A BUSHING IN ELEC. DISCONNECT TO AC UNIT
- PROVIDE AUDIBLE ALARM FOR DUCT SMOKE DETECTOR
- AIR BALANCE OK