Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL TESTED DUCT SMOKE DETECTOR |
|
| 05/06/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/01/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - SUPPORT REFER LINES ON ROOF - CONDENSORS NOT FUSED CORRECTLY - PROVIDE REDWOOD SLEEPERS UNDER CONDENSORS AND SECURD - PAINT EXPOSED PVC ON ROOF - PROVIDE A BUSHING IN ELEC. DISCONNECT TO AC UNIT - PROVIDE AUDIBLE ALARM FOR DUCT SMOKE DETECTOR - AIR BALANCE OK |