Permit: T07CM04760

Parcel: 128100810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04760

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
2. INSTALL GROUNDS PROPERLY IN DISCONNECTS FOR CONDENSING UNITS.
05/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS SPACE LOCKED
05/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRE ROOFTOP DISCONNECTS PROPERLY LINE/LOAD
2. INSTALL PROPER FUSES CONDENSING UNIT
3. NEED ROOFTOP GFI RECEPTACLE
4. PROPERLY STRAP SEAL TIGHT
5. NEED CIRCUIT FOR WALK IN LIGHTS
6. NEED PROPER CIRCUIT BREAKER FOR FRONT CASE
7. INSTALL RACEWAYS BETWEEN ALL BOXES WALK IN COOLERS
8. SEAL RACEWAYS INTO WALK IN COOLER
9. PROPERLY GROUND METAL BOXES
10. INSTALL PLATES ON SWITCHES WALK IN COOLERS