Permit: T07CM04752

Parcel: 141351540

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM04752

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
02/15/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
CANCELLED BECAUSE OF RAIN
02/14/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PLANS FOR ROOF
2) NAIL OFF FLOOR TRUSS SHEAR PANELS PER 303/508 DETAIL
3) STRAPS NEEDED AT SHEAR PANEL AT TOP OF STAIRS
4) TRIMMERS NEEDED
5) COMPLETE SHEAR AT BELLY BAND SOUTH EAST CORNER
6) T-BRACE 45 DEGREE ANGLE BRACE AT GABLE ENDS
7) NAIL OFF SHEAR PANELS IN RAFTERS PER PLAN
8) NAIL OFF SHEAR PANELS IN RAFTERS THROUGH ROOF