Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04744
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/14/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/13/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE ROOF JACK AT WATER LINE FEEDING MAKE UP AIR - SEAL ROOF JACKS AT EXHAUST AND MAKE UP AIR UNITS - MAKE UP AIR INLET TOO CLOSE TO VENTING, WASTE VENTS MUST BE 10' AWAY OR 2' ABOVE MAKE UP AIR INTAKE |