Permit: T07CM04744

Parcel: 13734001E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/05/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #7 & #8 OF PREVIOUS INSPECTION
05/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*CHECK ROOF NEXT TIME

1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS - 314.20
2. USE APPROVED HARDWARE WITH DEVICES - NOT DRYWALL SCREWS
3. TIMECLOCK DOOR BROKEN/MISSING HINGE
4. VERIFY SEAL FOR WALK-IN BOX PER 300.7
5. PLEASE VERIFY CORD & PLUG LISTING FOR WALK IN CONDENSOR - CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
6. EXIT LIGHT AT FRONT NOT WORKING
7. INTERIOR SIGNS: SIGNS NOT LISTED 600.3, 110.3B
a. SIGN DISCONNECT SWITCH TO BE CAPABLE OF
BEING LOCKED OUT - 600.6
b. NEED ACCESS 600.21 & SERVICE LIGHT 210.70
8. PANELS SCHEDULE & LOADS NOT AS PLANS
05/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CALL IN FOR FINAL INSP. AFTER POWER CHECK