Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/28/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAST BRACING TO BE THREADED INTO END 2. FINISH PREVIOUS ITEMS * A REFEE MAY BE ASSESSED IF WORK IS NOT COMPLETED |
|
| 01/24/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SERVICE & PANEL 1. IDENTIFY CONDUCTORS AT LUGS 2. INSTALL ALL STRANDS UNDER LUGS 3. RISER SUPPORTS BELOW ROOF NOT ATTACHED TO STRUCTURE 4. NO GENERAL LABELING OR ABBREVIATIONS - 408.4 5. LABEL OUTSIDE COVERS OF PANELS WITH A PERMANENT METAL LABEL 6. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 7. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 8. MAST BRACE ANCHORS TO BE INTO JOIST NOT ROOF SHEATHING INTERIOR & BUILDING 1. WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM 2. USE APPROVED WIRING METHODS FOR EXTERIOR LIGHTING ALSO, MUST MEET OUTDOOR LIGHTING CODES 3. PROVIDE APPROVED EXTENDER RINGS - 314.20 4. DO NOT PAINT SMOKE DETECTORS FINISH PREVIOUS ITEMS 2, 4 AND INTERIOR:1, 3, 5 FROM 1/16/08 INSP. |
|
| 01/16/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/15/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |