| 01/18/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 01/17/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) AT ALL SHEARWALLS NAIL DBL END STUDS OSB 2) ALL SHEAR WALLS TRANSFER TO TRUSS NAIL TOP CHORD TO ROOF DECK 6" ON CENTER 8D OR 4" ON CENTER STAPLES 3) FINISH BLOCKS, AT DRYWALL SHEARWALLS |