Permit: T07CM04723

Parcel: 140252400

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/13/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/07/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A35 ANGLE CLIP PER DETAIL (1) ON ROOF FRAMING NOT PER PLAN ON SOUTHSIDE OF HOUSE DUE-TO TRUSS ENGINEERING. NEED ENERGINEERING SHOWING HOW THEY WANT CONNECTION TO TOP PLATE
2) A35 NOT NAILED AT NORTH END OF HOUSE PER DETAIL (1)
3) DETAIL (2) TYPICAL END TRUSS NOT PER PLAN-BRACES ON WEST END NEEDS TO BE MORE AT A 45 DEGREE-2 X 4 BLOCK NOT PER PLAN
4) MISSING RAT RUN BRACING PER TRUSS CALCS (B01)
5) NEED TO VERIFY LTP4 CLIPS UNDER OSB AT WEST AND EAST END OF TRUSS TO WALL CONNECTION PER PLAN DETAIL (2)
03/04/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*