Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04713
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C CABLE AT SHALLOWS ALSO PVC 2. NO MORE THAN 360 DEG. IN CONDUIT RUNS 3. NEED LETTER AUTHORIZING USAGE OF AC CONDUITS OK EXTERIOR WALLS & LIGHTS OK PVC UNDERGROUND SUBJECT TO LETTER |
|
11/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEMP POWER TEC COMM SUBJECT TO POSTING OF BOND |
|
10/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BONDING JUMPER TO BE PER 250.102 2. PLEASE PROVIDE INSTRUCTION BOOK TO VERIFY IF BRACING IS REQUIRED *RECEIVED LETTER OF TORQUE |
|
09/10/2008 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
05/21/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE ADD 02010 TO PERMIT 2. THERE IS DAMAGED PVC CONDUIT ON WEST END OF BUILDING OK 4 - 2 1/2 + 1 - 4" UNDER FLOOR COL. E-F & COL. 2-4 OK UNDER MAIN ELECTRIC ROOM |