Permit: T07CM04696

Parcel: 12419037A


Addresses:

1755 E WINSETT ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/20/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CANOPY GROUNDING PER "EMERSON" TEST
2. GFI MAIN TEST OK. RECEIVED DOCUMENTS.
3. NEED ITEM #4
4. LETTER FOR COMPLIANCE OF NEC 514.11, 514.13 FROM CONTR. OR ENGINEER OF RECORD
5. EQUIP. IN COMPLIANCE WITH NFPA 70 PER MANUF. CIRC. OF COMP.
6. NEED PERMIT FOR GEN AND INSPECTION
02/24/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL SECONDARYS AT SES
2. GFI MAINS TO BE TESTED ON SITE PER 230.95 NEC
3. UFER & MAIN BONDING JUMPER OK
4. LETTER FROM ARCH. FOR DELETION OF COMPRESSOR #2
5. NEED TO VERIFY BONDING OF CANOPY STRUCTURE
6. SEAL OFF'S NOT POURED YET, LETTER FOR 514.11, 514.13
12/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONTR. REQUEST AFTER HRS. UNSCHEDULED INSP.
PAID $150.00 CK#1835

OK PAD GROUNDING & REBAR 2 PADS