Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CANOPY GROUNDING PER "EMERSON" TEST 2. GFI MAIN TEST OK. RECEIVED DOCUMENTS. 3. NEED ITEM #4 4. LETTER FOR COMPLIANCE OF NEC 514.11, 514.13 FROM CONTR. OR ENGINEER OF RECORD 5. EQUIP. IN COMPLIANCE WITH NFPA 70 PER MANUF. CIRC. OF COMP. 6. NEED PERMIT FOR GEN AND INSPECTION |
|
| 02/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL SECONDARYS AT SES 2. GFI MAINS TO BE TESTED ON SITE PER 230.95 NEC 3. UFER & MAIN BONDING JUMPER OK 4. LETTER FROM ARCH. FOR DELETION OF COMPRESSOR #2 5. NEED TO VERIFY BONDING OF CANOPY STRUCTURE 6. SEAL OFF'S NOT POURED YET, LETTER FOR 514.11, 514.13 |
|
| 12/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONTR. REQUEST AFTER HRS. UNSCHEDULED INSP. PAID $150.00 CK#1835 OK PAD GROUNDING & REBAR 2 PADS |