Permit: T07CM04694

Parcel: 10713128C


Addresses:

2608 N BALBOA AV

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
01/22/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/18/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BRACED WALL PANELS ON EAST WALL NEEDS TO EXTEND FROM SOLE PLATE TO BOTTOM OF RAFTER
01/16/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWN AT ENTRY OFF OF LAUNDRY ROOM, NEED TO NAIL DBL STUD ALL THE WAY UP TO ROOF
2) SOUTHWEST CORNER NEEDS 2 ANCHOR BOLTS
3) EAST BEARING WALL CALLS FOR 2" X SOLID BLOCKING BETWEEN ? RAFTER WITH 2" SCREEN VENTING HOLES
4) SHEAR PANELS ON EAST WALL, NEED TO GO UP TO BOTTOM OF RAFTERS
5) OK TO DRY ROOF IN