| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/12/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* O.S.A SATISFIED, SEE BUILDING INSPECTOR FOR TEMP C OF O AIR BALANCE REPORT OK |
|
| 11/10/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE RUBBER GROMMETS WHERE LINE SETS ENTER UNITS 2. C.U's NOT FUSED 3. REMOVE TILES AT A.H UNITS ABOVE CEILING 4. PROVIDE AIR BALANCE REPORT PER PLANS 5. LABEL ALL EQUIPMENT PER MECHANICAL SCHEDULE |
|
| 10/30/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |