Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04648
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/12/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* O.S.A SATISFIED, SEE BUILDING INSPECTOR FOR TEMP C OF O AIR BALANCE REPORT OK |
|
11/10/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE RUBBER GROMMETS WHERE LINE SETS ENTER UNITS 2. C.U's NOT FUSED 3. REMOVE TILES AT A.H UNITS ABOVE CEILING 4. PROVIDE AIR BALANCE REPORT PER PLANS 5. LABEL ALL EQUIPMENT PER MECHANICAL SCHEDULE |
|
10/30/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |