Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07CM04648
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
10/24/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OK POLE BASE 2. NEED TO EXPOSE PVC RACEWAY FOR INSPECTION ALONG ENTIRE LENGTH. INSPECTION OF UNDERGROUND INSTALLATION IS NOT JUST LOOKING AT ENDS WHERE RACEWAY EMERGES |
|
06/25/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 2/0 CU UFER TIED TO FOOTING REBAR OK WITH CLAMP @ SE CORNER |