Permit: T07CM04648

Parcel: 99999999A


Addresses:

3682 S WALL ST


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T07CM04648

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2008 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
SPECIAL INSPECTION
10/06/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH/EAST SITE WALL @ DRIVE
10/03/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. DUMPSTER FOOTING OK
NEEDS 3 CORNER BARS AND 2 AT THE ENDS
2. LOADING DOCK FOOTINGS OK (412) S400
08/21/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. 5 CONCRETE COLUMNS AT FRONT OF BLDG. 406 ON 5400
2. INTERIOR COLUMNS DRY PACKED AND BOLTED
3. SPECIAL INSPECTED
08/15/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
CLOSURE POUR @ INSIDE PERIMETER WALLS W/COLUMNS
08/13/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection NO PLANS
NO SUPER
08/12/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
07/22/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. TILT PANELS 2, 4, 6, 9, 13, 14, 15, 16
2. SPECIAL INSPECTED C TECH
3. 2' STEM WALLS AT A-1 ON A1.8
07/18/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
TILT PANELS INSPECTION 7/17
07/17/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PANELS 12, 11, 10, 8, 7, 3, 5, 1 -- OK TO POUR

1. SPECIAL INSPECTED
2. NEED ENGINEERED STAMPED RFI FOR EPOXY BOLTS AND REBAR SLAB DOWELS - PANELS 10 & 5
07/16/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
07/01/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
EXTERIOR WALL FOOTINGS EXCEPT DOCK OK TO POUR

1. STRUCTURAL RFI's NEED ENG. STAMP
WAITING ON RFI FROM 6/25
06/25/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH EXTERIOR FOOTING OK TO POUR
06/24/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
06/18/2008 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
23 INTERIOR F3, F4, F5, F6, F8 INTERIOR COLUMN FOOTINGS
SPECIAL INSPECTED
06/17/2008 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEEDS SPECIAL INSPECTION ON ALL REINFORCED CONCRETE
2. FOOTINGS NOT CORRECT THICKNESS