Permit: T07CM04638

Parcel: 106101650


Addresses:

4000 N SUN TRAN BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04638

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/06/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CIELING TILES 1ST AND 2ND FLEERS WITH THE EXCEPTION OF AREAS WITH LINEAR DIFFUSERS, INSULATE LINEAR DIFFUSERS TO A MIN. R 4.2
HURIZ. B-VENT NOT TO EXCEED 75 DEGREES TOTAL VERT. RISE AND NOT LESS THAN 60 DEGREES
07/02/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR SHEETROCK ELEVATOR LOBBY 1ST AND 2ND FLOOR
07/01/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT IS TIED TO EMT WITH BAILING WIRE
2) DUCT NOT WRAPPED
3) BOOT NOT SEALED OR WRAPPED
06/24/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE ACCESS TO DISCONNECT PER NEC
05/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
NO COMBUSTIBLE MATERIAL ALLOWED IN PLENUM CEILING
OK FOR RESTROOMS 1ST FLR ROCK
05/13/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 1" CLEARANCE TO COMBUSTIBLE ON ALL B-VENT
2) SEAL ALL DUCT JOINTS INCLUDING RISERS
3) COMPLETE DUCT SYSTEMS
4) COMPLETE LIST DATED 5/6/09
05/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/06/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. TU-14 PROVIDE PROPER ACCESS
2. MED. PRESSURE DUCT TO TU-13 NOT PROPERLY SUPPORTED - SUPPORT ALL DUCT PER IMC AND SMACNA
3. TU-9 RELOCATE UNIT FROM PLANE OF WALL & SEAL
ALL DUCT
4. SEAL JOINTS AT TU-8
5. SEAL ALL DUCT JOINTS
6. VERIFY LOCATIONS OF SUPPLY AND EXHAUST GRILLS IN RESTROOMS
7. BRANCH DUCTS ARE NOT TO BE SUPPORTED
BY BRANCH TAPS
8. OK TO INSTALL ALL GRID
02/25/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/24/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/24/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*