Permit: T07CM04638

Parcel: 106101650


Addresses:

4000 N SUN TRAN BL


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM04638

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/02/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/31/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK ROUGH WALLS 1ST FLOOR FOREMAN & LABOR ROOMS
2. OK 2ND FLOOR EAST EXCEPT SERVICE CONDUITS TO COMPLY WITH 230-70 A-1
03/26/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE TO POLE AND POLE BASE AS MARKED
03/17/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUIT AND POLE BASE AS MARKED
03/16/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS UNDERGROUND
AND POLE BASE AS MARKED
03/11/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE TO POLE AS MARKED
03/09/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES & PVC POLE TO POLE
AS MARKED ON PLANS
03/06/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES AS MARKED
OK POLE TO POLE AS MARKED
OK CENTER WALL ABOVE BLOCK
03/03/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE TO POLE AS MARKED
01/29/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
NOTE: SERVICE & RACEWAY TO BE AS PER 230.70(A)(1) & 230.6
01/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1 - 2" & 1 - 1" BUILDING NORTH 60' FROM COMM. ROOM
OK 2 - 1" TO HYDRAULIC PUMP MOTOR
OK TEMP CABLE IN TRENCH
12/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC UNDER SLAB COLUMNS F-J
OK 2ND & 3RD LIFTS WEST END
12/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUIT FROM PANELS
IN CENTER AREA TO AND THROUGH EAST AREA FOR UPSTAIRS

NOTE: 3" & 4" PVC CONDUITS AT 360 DEG. NOW
12/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS DOWN CENTER BAY AREAS WALL TO WALL
12/05/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2" SLEEVE TO SUMP PUMP
1. FINISH DOWN CENTER
11/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/31/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/04/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 10 - 4" PVC & RIGID 90 DEG's
TEP TO INSIDE BUILDING
OK 2 - 2" PVC BUILDING OUT 10' & 90 DEG's
OK PVC IN WALLS 1ST FLOOR
09/02/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED
08/29/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANNOT LOCATE
08/20/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED
07/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. 1 PAIR 5' PVC FROM MH#5 TO TRANSFORMER AND BACK TO INTERCEPT OK TO SLURRY
2. REPAIR AT INITIAL INTERCEPT WEST OF EXISTING PULL BOX OK TO SLURRY
3. FROM NEWLY REMOVED PULL BOX TO TRANSFORMER
(WEST OF MH4) OK TO SLURRY

PRIVATE PRIMARY PULLS

REF. PP E1.2