Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04637
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/01/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
08/06/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CLEANOUT BLOCKED 2) CHILL WATER PIPING NOT INSULATED 3) PROVIDE SECONDARY DRAIN 4) USE SCREWS TO FASTEN FLEX TO GRILLS |
|
05/13/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL DUCT JOINTS 2) CONDENSATE CLEANOUTS NOT ACCESSIBLE 3) INSULATE CONDENSATE PIPING PER PLANS AND SPECS 4) PROVIDE DAMPERS AT RAND BRANCH TAPS 5) PROVIDE STRAPS PER SMACNA 6) COMPLETE DUCT SYSTEMS |