Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04636
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) MECHANICALLY FASTEN RETURN GRILL FOR SEISMIC RESTRAINT 2) COMPLETE PIPING INSULATION |
|
07/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
06/18/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BRANCH DUCT DRIVES NOT COMPLETE, JOINTS NOT SEALED 2) H/W AND L/W PIPING NOT INSULATED 3) DUCT TOUCHING COPPER PIPE 4) DUCT NOT COMPLETE 5) HYDRO TEST TO FAN COILS OK-100 PSI |
|
05/20/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |