Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM04636
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2009 | MECHANICAL - INTERMEDIATE | Approved | ||
10/07/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/06/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEMS DISCUSSED |
|
09/01/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE ALL HYDRO PIPING 2) COMPLETE FC UNITS ELECTRICAL 3) COMPLETE FC UNITS DUCT WORK |
|
07/22/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHILL SUPPLY AND RETURN IN BLDG 3 MECH ROOM PRESSURE TEST OK, OK TO INSULATE |
|
05/20/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BLDG. 2 CONNECTION UNDERGROUND TO MECHANICAL ROOM ISOLATION VALVES HYDRO TEST @ 150 PSI OK |