Permit: T07CM04636

Parcel: 106101650


Addresses:

3930 N SUN TRAN BL


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM04636

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/04/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1" CONDUITS U.G. FOR WEST & EAST CANOPY PV SYSTEMS
05/01/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 2" AND 1" AND 1" FOR LTG. UNDER CANOPY FROM "PVH1" BY CORONA ELEC. CONTR. EXCEPT SOUTH TRENCH
2. PV POWER BY BROCKETT ELEC. CONTR.
01/29/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK LAST OF RUN TO PULL BOX 150'
01/22/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
TRENCH NEEDS TO BE DUG BACK UP
12/03/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED
12/02/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 120' NORTH EAST TO WALL PVC CONDUITS
OK 110' NORTHWEST PVC CONDUITS
11/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC 3 CHILLERS
10/30/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS FEEDER & DATA UNDER SLAB
TO ELECTRIC ROOMS
09/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 3 - 2" PVC 110' ELECTRIC ROOM TO END OF BUILDING
09/23/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 5 - 4" PVC & RIGID 90 DEG.'s
TRANSFORMER TO SES