Permit: T07CM04635

Parcel: 106101650


Addresses:

3920 N SUN TRAN BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM04635

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/06/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) COMPLETE ITEMS DISCUSSED
09/01/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NOTE #2 FROM 6/5/09 REQUIRES EXTRA HANGERS OVER HEAD, HAVE ALL AREAS REGARDING EXTRA HANGERS OPEN FOR INSPECTION
2) ROOF DRAINS HAVE NOT BEEN APPROVED, HAVE ALL AREAS WHERE THERE ARE RAIN WATER LEADERS OPEN FOR INSPECTION
3) PROVIDE REVISED APPROVED PLAN FOR FLOOR SINK (3/2/09) AND CALL IN ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
4) HYDRO PIPING IN MECHANICAL ROOM OK ON PRESSURE TEST
5) OK TO INSUALTE
6) PROVIDE APPROVED COMBUSTION AIR SYSTEM FOR WATER HEATER
08/26/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK FOR TILES
08/25/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) HYDRO PIPING TEST BELOW 100 PSI
08/18/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/30/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/24/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
NO ROCK AT AREA WITH T.U. UNITS
NO ROCK AT FIRE DAMPERS TO MECH. RM.
06/23/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TU-13 VERIFY ACCESS DOOR OPENS
2. TU-16 VERIFY ACCESS DOOR OPENS
3. VERIFY CLEARANCE ON ALL TU UNITS ACCESS AND
PROVIDE 36" CLEARANCE BACK FROM DISCONNECT
4. ALL DUCT NOT SEALED
5. INSTALL RETAINING CLIPS ON DUCT FLANGES
6. SUPPORT RETURN DUCT IN MECH. ROOM OFF OF FLEX
05/20/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
HYDRONIC PIPING SYSTEM UNDERGROUND FROM
WEST FUTURE TO CONNECTION TO BUILDING (3)
HYDRO TEST @ 150 PSI OK