Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM04635
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/06/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEMS DISCUSSED |
|
09/01/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOTE #2 FROM 6/5/09 REQUIRES EXTRA HANGERS OVER HEAD, HAVE ALL AREAS REGARDING EXTRA HANGERS OPEN FOR INSPECTION 2) ROOF DRAINS HAVE NOT BEEN APPROVED, HAVE ALL AREAS WHERE THERE ARE RAIN WATER LEADERS OPEN FOR INSPECTION 3) PROVIDE REVISED APPROVED PLAN FOR FLOOR SINK (3/2/09) AND CALL IN ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL 4) HYDRO PIPING IN MECHANICAL ROOM OK ON PRESSURE TEST 5) OK TO INSUALTE 6) PROVIDE APPROVED COMBUSTION AIR SYSTEM FOR WATER HEATER |
|
08/26/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK FOR TILES |
|
08/25/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) HYDRO PIPING TEST BELOW 100 PSI |
|
08/18/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/30/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/24/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO ROCK AT AREA WITH T.U. UNITS NO ROCK AT FIRE DAMPERS TO MECH. RM. |
|
06/23/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TU-13 VERIFY ACCESS DOOR OPENS 2. TU-16 VERIFY ACCESS DOOR OPENS 3. VERIFY CLEARANCE ON ALL TU UNITS ACCESS AND PROVIDE 36" CLEARANCE BACK FROM DISCONNECT 4. ALL DUCT NOT SEALED 5. INSTALL RETAINING CLIPS ON DUCT FLANGES 6. SUPPORT RETURN DUCT IN MECH. ROOM OFF OF FLEX |
|
05/20/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HYDRONIC PIPING SYSTEM UNDERGROUND FROM WEST FUTURE TO CONNECTION TO BUILDING (3) HYDRO TEST @ 150 PSI OK |