Permit: T07CM04633

Parcel: 133124550

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04633

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND BUSHING FOR DISCONNECT 250.97
2. FINISH ITEMS 1 & 3 PREVIOUS INSPECTION
04/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
04/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
2. USE APPROVED WIRING METHODS FOR OUTSIDE CEILING FANS
3. PLANS NEED REVISIONS FOR PANEL SCHEDULE & LOAD CALCULATIONS PLEASE SHOW CORRECT BREAKERS FOR REWIRED EQUIPMENT IN OTHER PANELS ALSO.
WE HAVE 3 - POLE BREAKERS ON 2 POLE CIRCUITS
ALSO TO EQUIPMENT

ROOF:
1. MAINTAIN WORKING CLEARANCES AT ALL DISCONNECTS
2. USE APPROVED FITTINGS AT JUNCTION BOX
3. FUSE ALL CONDUCTORS AT DISCONNET FOR HOOD
4. USE TERMINAL END FOR STRANDED CONDUCTORS
04/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*