Permit: T07CM04633

Parcel: 133124550

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04633

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
WHERE ARE SHORT TRIP BREAKERS AS PER REVISED PLANS

OK REVISED PLANS & STAMPS
OK PREVIOUS ITEMS
04/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/08/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
04/03/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/01/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*CHECK ROOF NEXT TIME

1. RECEPTACLES AND DEVICES TO BE INSTALLED IN APPROVED BOXES
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING - 314.20
3. MISSING COVER PLATE
4. GROUND JUNCTION BOXES
5. SUPPORT MC CABLES AS PER 330.30
6. EXPOSED CONDUCTORS AND UNAPPROVED WIRING METHOD
7. INSTALL EQUIPMENT GROUNDING CONDUCTORS AS PER MANUFACTURES OF HOOD CONTROL CABINET
8. PLEASE REVISE CIRCUIT DIRECTORIES AS PER 408.4
9. STEAM TABLE NOT AS PER PLANS
10. FILL UNUSED OPENINGS IN BOXES
03/21/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
02/20/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP MC CABLE WITHIN 12" OF BOXES
2. PLAN CALLS FOR STEAM TABLE TO BE FED
WITH #8 CONDUCTORS TO DISCONNECT
3. INSTALL MUD RING FOR MICROWAVE RECEPTACLE