Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04633
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WHERE ARE SHORT TRIP BREAKERS AS PER REVISED PLANS OK REVISED PLANS & STAMPS OK PREVIOUS ITEMS |
|
04/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/08/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
04/03/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/01/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* *CHECK ROOF NEXT TIME 1. RECEPTACLES AND DEVICES TO BE INSTALLED IN APPROVED BOXES 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING - 314.20 3. MISSING COVER PLATE 4. GROUND JUNCTION BOXES 5. SUPPORT MC CABLES AS PER 330.30 6. EXPOSED CONDUCTORS AND UNAPPROVED WIRING METHOD 7. INSTALL EQUIPMENT GROUNDING CONDUCTORS AS PER MANUFACTURES OF HOOD CONTROL CABINET 8. PLEASE REVISE CIRCUIT DIRECTORIES AS PER 408.4 9. STEAM TABLE NOT AS PER PLANS 10. FILL UNUSED OPENINGS IN BOXES |
|
03/21/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
02/20/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP MC CABLE WITHIN 12" OF BOXES 2. PLAN CALLS FOR STEAM TABLE TO BE FED WITH #8 CONDUCTORS TO DISCONNECT 3. INSTALL MUD RING FOR MICROWAVE RECEPTACLE |