Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04572
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EXCEPT CONTROLLER ON EAST SIDE OF GATE |
|
05/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDUIT TO SHALLOW AT J-BOX AT STARR PASS INTERSECTION AND AT GATE OPERATORS - EXPOSE CONDUITS FOR POWER AT 50' INTERVALS AND GATE POWER, CONTROL CONDUITS AT ALL GATE & CONTROL PAD OPERATORS. DEPTH PER 300.5 NEC - PROVIDE APPROVED PLANS |
|
05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RECALL INSP. EXPOSE CONDUITS AS PER NOTES LAST INSP. IVR DOWN |
|
04/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CODE CONDUIT DEPTH IS 18" MIN. 24" AT ROADWAY CROSSINGS. HAVE CONTR. ON SITE TO REMOVE COVERS AND EXPOSE CONDUITS - ALL UNDERGROUND COVERED PRIOR TO INSPECTION |