Permit: T07CM04572

Parcel: 11627504B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04572

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EXCEPT CONTROLLER ON EAST SIDE OF GATE
05/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONDUIT TO SHALLOW AT J-BOX AT STARR PASS INTERSECTION AND AT GATE OPERATORS
- EXPOSE CONDUITS FOR POWER AT 50' INTERVALS AND GATE POWER, CONTROL CONDUITS AT ALL GATE & CONTROL PAD OPERATORS. DEPTH PER 300.5 NEC
- PROVIDE APPROVED PLANS
05/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECALL INSP. EXPOSE CONDUITS AS PER NOTES LAST INSP.

IVR DOWN
04/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CODE CONDUIT DEPTH IS 18" MIN. 24" AT ROADWAY CROSSINGS. HAVE CONTR. ON SITE TO REMOVE COVERS AND EXPOSE CONDUITS
- ALL UNDERGROUND COVERED PRIOR TO INSPECTION