Permit: T07CM04570

Parcel: 136261300

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T07CM04570

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
06/30/2008 MECHANICAL - HOODS Approved
06/23/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
SECOND LAYER OF GREASE DUCT WRAP AND BANDING OK
06/19/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
BUILD ACCESS DOOR PER INSTALL INSTRUCTIONS
FINISH 2ND LAYER OF FIRE WRAP
06/18/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
06/17/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1ST LAYER OF DUCT WRAP OK
06/13/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCT OK FOR 1ST LAYER OF FIRE WRAP
06/11/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
06/10/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CLEANOUT OPENING TO BE MIN. 12" ON EACH SIDE AS PER SECTION 506.3.9 2006 IMC AND MUST BE ACCESSIBLE
NUMEROUS LEAKS IN GREAE DUCT
TERMINATE CONDENSATE FROM NEW UNIT TO AN APPROVED LOCATION