Permit: T07CM04570

Parcel: 136261300

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM04570

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED BACTERIA REPORT FOR POTABLE WATER IN BLD.

1. PROVIDE CORRECT DRAINAGE
FOR 2 BOWLS OF 3 COMP SINK

NOTE: ONLY (1) P-TRAP PER TRAP ARM AND YOU CANNOT REDUCE DRAINAGE SIZE.

REINSPECTION P.M.
06/19/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3-COMP SINK, REQUIRES WASH & RINSE BOWLS GO TO DIRECT CONNECTION TO GREASE WASTE AND SANITIZE BOWL GOES TO INDIRECT RECEPTOR WITH 1" AIR GAP
2. PROVIDE CLEAN BACTERIA REPORT FOR POTABLE WATER
04/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
THIS INSPECTION FOR PIPING FROM GREASE LINE THRU INTERCEPTOR AND TO BUILDING SEWER OK
PROVIDE TRACER WIRE ON THIS PIPING - PRIOR TO BACKFILL

NOTE: INTERCEPTOR VENT SHALL TERMINATE MINIMUM 1' FROM BUILDING WALL OR EXTEND TO 6" ABOVE TOP OF WALL