Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL 15a & 20a RECEPT 120V TO BE GFI PROTECTED IN KITCHEN 2. INSTALL ALL MOUNTING SCREWS INDUSTRIAL COVERS 3. PROPERLY FUSE ROOFTOP EQUIPMENT 4. CANNOT USE GREEN WIRE FOR PHASE CONDUCTORS 5. INSTALL CEILING TILES SO PLATES CAN BE INSTALLED ON RECEPTACLES. |