Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04567
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/16/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. DUCT DETECTOR NOT WIRED TO SHUT DOWN AT 1 MIN. 2. CONTAINMENT TEST FAILED 3. SEE ITEM 3 DATED 5/27/09 4. SEE ITEMS 5 AND 6 DATED 5/27/09 |
|
05/27/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. INTERLOCK EXHAUST FANS AS PER EQUIPMENT SCHEDULE 2. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE 3. EXTEND WATER HEATER VENT MIN. 2' ABOVE PARAPET 4. RELOCATE ELEC. DISCONNECTS BLOCKING SERVICE PANELS 5. NEED TO TEST DUCT SMOKE DETECTORS 6. NEED TO DO A CAPTURE AND CONTAINMENT TEST 7. MAKE UP AIR MUST BE INTERLOCKED WITH EXHAUST FANS 8. AIR BALANCE IS OK 9. CONTRACTOR PROVIDE SMOKE 10. OK FOR CEILING TILES 11. PROVIDE ECONOMIZERS AS PER PLAN |
|
03/04/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* DOORS LOCKED. NO ACCESS. |