Permit: T07CM04567

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM04567

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/16/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. DUCT DETECTOR NOT WIRED TO SHUT DOWN AT 1 MIN.
2. CONTAINMENT TEST FAILED
3. SEE ITEM 3 DATED 5/27/09
4. SEE ITEMS 5 AND 6 DATED 5/27/09
05/27/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. INTERLOCK EXHAUST FANS AS PER EQUIPMENT SCHEDULE
2. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE
3. EXTEND WATER HEATER VENT MIN. 2' ABOVE PARAPET
4. RELOCATE ELEC. DISCONNECTS BLOCKING SERVICE PANELS
5. NEED TO TEST DUCT SMOKE DETECTORS
6. NEED TO DO A CAPTURE AND CONTAINMENT TEST
7. MAKE UP AIR MUST BE INTERLOCKED WITH EXHAUST FANS
8. AIR BALANCE IS OK
9. CONTRACTOR PROVIDE SMOKE
10. OK FOR CEILING TILES
11. PROVIDE ECONOMIZERS AS PER PLAN
03/04/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
DOORS LOCKED. NO ACCESS.