Permit: T07CM04567

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T07CM04567

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2009 MECHANICAL - HOODS Approved IVRS - Inspection :*
06/16/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
04/17/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
03/25/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1. FLEX DUCTS NOT SEALED OR SUPPORTED PER PLAN.
2. DIFFUSERS NOT SUPPORTED PER PLAN
3. YOU CANNOT CONNECT FLEX DUCT TO THIS TYPE OF DIFFUSER WITHOUT A BEADED COLLAR INSTALLED ON NECK OF DIFFUSER
4. HIGH EFFICIENCY TAKE-OFF's WERE NOT USED
5. PROVIDE LETTER FROM ENGINEER IF CHANGING ANY DETAILS.
02/02/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
01/30/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1. 2ND LAYER OF FIRE WRAP IS OK
2. 1 BAND WITHIN 1 1/2" OF EDGE OF WRAP IS MISSING ON SMALL HOOD DUCT.
3. WILL CHECK ON NEXT VISIT
01/23/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK 1ST LAYER OF FIRE WRAP
OK FOR 2ND LAYER & INSTALL HOOD
BE SURE FIRE WRAP EXTENDS MIN. 18" ABOVE ROOF
01/22/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK FOR 1ST LAYER OF FIRE WRAP