Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T07CM04567
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2009 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
06/16/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
04/17/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
03/25/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1. FLEX DUCTS NOT SEALED OR SUPPORTED PER PLAN. 2. DIFFUSERS NOT SUPPORTED PER PLAN 3. YOU CANNOT CONNECT FLEX DUCT TO THIS TYPE OF DIFFUSER WITHOUT A BEADED COLLAR INSTALLED ON NECK OF DIFFUSER 4. HIGH EFFICIENCY TAKE-OFF's WERE NOT USED 5. PROVIDE LETTER FROM ENGINEER IF CHANGING ANY DETAILS. |
|
02/02/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
01/30/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1. 2ND LAYER OF FIRE WRAP IS OK 2. 1 BAND WITHIN 1 1/2" OF EDGE OF WRAP IS MISSING ON SMALL HOOD DUCT. 3. WILL CHECK ON NEXT VISIT |
|
01/23/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* OK 1ST LAYER OF FIRE WRAP OK FOR 2ND LAYER & INSTALL HOOD BE SURE FIRE WRAP EXTENDS MIN. 18" ABOVE ROOF |
|
01/22/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* OK FOR 1ST LAYER OF FIRE WRAP |