Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04567
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/16/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/20/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* VAPOR BARRIERS STILL NOT PROPERLY SEALED. USE ONLY UL181 TAPES AND MASTICS. HIGH EFFICIENCY TAKE-OFF's WERE NOT USED PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS OR PLANS |
|
04/17/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* DUCTING NOT INSTALLED PER DETAILS ON PLANS DIFFUSERS NOT SUPPORTED, DUCTS NOT SEALED AT FLEX CONNECTIONS. PROVIDE LETTER FROM ENGINEER IF CHANGING DETAILS. |
|
03/25/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/10/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES. PROVIDE CONDENSATE DRAINS. WILL CHECK ON FINAL. |
|
02/04/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |