Permit: T07CM04567

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04567

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/16/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/20/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
VAPOR BARRIERS STILL NOT PROPERLY SEALED.
USE ONLY UL181 TAPES AND MASTICS.
HIGH EFFICIENCY TAKE-OFF's WERE NOT USED
PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS OR PLANS
04/17/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
DUCTING NOT INSTALLED PER DETAILS ON PLANS
DIFFUSERS NOT SUPPORTED, DUCTS NOT SEALED AT FLEX CONNECTIONS. PROVIDE LETTER FROM ENGINEER IF CHANGING DETAILS.
03/25/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/10/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES.
PROVIDE CONDENSATE DRAINS.
WILL CHECK ON FINAL.
02/04/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*