Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT INDIRECT DRAINS & PROVIDE 1" MINIMUM AIR GAP 2. PROVIDE SEPARATE FULL SIZE DRAINS FOR ICE MAKER AND ICE STORAGE 3. PROVIDE FULL SIZE 1/2 WATER TO CARBONATOR AND WATER DISPENSER BACKFLOW DEVICES 4. MAKE ALL FIXTURES WATER TIGHT AT FLOOR AND WALL 5. COMPLETE INSTALL OF BEVERAGE DISPENSER 6. INSTALL DOMES IN FLOOR SINKS 7. PAINT VENTS ON ROOF 8. PROVIDE STERILIZATION REPORT |
|
| 03/26/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CALL IN ALL PLUMBING INSPECTIONS FOR APPROVAL 2. COMPLETE ALL PLUMBING & APPLIANCE INSTALLS THAT REQUIRE PLUMBING 3. WALKED WITH PLUMBER. 4. THIS IS NOT A PUNCH LIST THIS INSPECTION FOR 03050 - TEST ON PIPING OK PARTIAL TEST ON INTERCEPTOR INLET & OUTLET OK |
|
| 03/04/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALL IN ALL PLUMBING INSPECTIONS ON YOUR ACTIVITY CARD FOR APPROVAL PRIOR TO FINAL. NO ACCESS LOCKED 11:13 |