Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04567

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/22/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CANNOT USE EXTENSION CORDS AS PERMANENT WIRING METHOD. REMOVE CORDS AND INSTALL HARDWIRED TO ELECTRICAL SYSTEM
2) CHECK WITH BLDG INSPECTOR FOR TCO
07/21/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
07/16/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/15/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MISSING EM LIGHTS
2. INSTALL EXTENSION ON BOXES MORE THAN 1/4" BACK
3. NEED PANEL DIRECTORIES
4. NEED REVISED PLANS THAT REFLECT ACTUAL SCOPE OF WORK INSTALLED
5. MOUNT RECEPTACLE TO FLOOR FOR SALAD BUFFET
6. OK CEILINGS
06/11/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF INSPECTION ONLY -- NEED ROOFTOP GFI
03/05/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/04/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MEETING TO DISCUSS PROJECT. ENSURE APPROVED PLANS REFLECT ACTUAL WORK DONE.