Permit: T07CM04566

Parcel: 141113810

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
06/27/2011 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
07/07/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) OK GROUND RODS
2) REVISE PLANS FOR CHANGE TO SERVICE
3) BOND BLDG STEEL AND WATER
4) CONNECT BONDING JUMPER IN METER CAN
5) CONNECT UFER TO SERVICE
05/28/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
OK 1 - 4" PVC FROM TEP XFMR TO SES LOCATION
02/12/2009 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*