Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2011 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 07/07/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) REVISE PLANS FOR CHANGE TO SERVICE 3) BOND BLDG STEEL AND WATER 4) CONNECT BONDING JUMPER IN METER CAN 5) CONNECT UFER TO SERVICE |
|
| 05/28/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK 1 - 4" PVC FROM TEP XFMR TO SES LOCATION |
|
| 02/12/2009 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |