Permit: T07CM04554

Parcel: 11618324P

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM04554

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL PVC EXPOSED TO EXTERIOR TO BE PAINTED WITH LATEX PAINT
2. ROMEX CONNECTOR AT EVAP UNIT NOT INSTALLED
3. MARK DATA PLATES ON UNITS
4. PROVIDE FILTERS IN O.S.A
5. OPEN OSA TO 2/3 OPEN
04/25/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSATE FROM AC UNIT CANNOT DRIP OUT OF A SCUPPER
TERMINATE TO WITHIN 6" OF THE GROUND
MARK UNIT DATA PLATE WITH PROPER HEAT STRIP
INSTALLED AND FUSE ACCORDINGLY
PROVIDE A ROMEX CONNECTOR ON EVAP COOLER CORDS
PROVIDE AN AIR BALANCE REPORT