Permit: T07CM04554

Parcel: 11618324P

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04554

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/22/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
FLANGE OK
04/21/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET BEND REQUIRES "DUTCHMAN"
04/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLUMBER FORGOT TO REDLINE P-3 ON PLAN
2. OK TO COVER UNDERGROUND
OK TO COVER WALLS

WILL RECHECK CLOSET FLANGE AFTER FLOOR IS POURED
BUT BEFORE WC IS SET
04/07/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NO APPROVED PLAN ON SITE
2. NO REDLINES OF CHANGES
3. REQUIRE FULL SIZE UPPER TERMINAL CLEANOUT
4. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
03/31/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/18/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE CORRECT DRAINAGE FOR LAV & SINK

NOTE: NO VENT CAN SERVE AS A DRAIN

PROVIDE LONG RADIUS FITTINGS FOR
HORIZONTAL X HORIZONTAL CHANGE OF DIRECTIONS
03/06/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO CHANGE FROM LAST INSPECTION
* SEC 311.4 2006 UPC - WASTE PIPE MAY NOT DUMP
INTO A VENT
* SEC 707.6 2006 UPC - CLEANOUTS SHALL BE INSTALLED VERTICALLY, ABOVE THE FLOW LINE OF THE PIPE

SANTEE MAY NOT BE INSTALLED ON ITS SIDE
ONLY ONE TRAP ON A TRAP ARM 1001.1 2006 UPC
SEE 1002.1 2006 UPC EACH FIXTURE TRAP TO HAVE A VENT
CONTRACTOR TO PAY REINSPECTION FEE
02/29/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NOT INSTALLED PER PLAN
- NOT INSTALLED PER CODE
- CAP OFF ALL OPEN PIPING IMMEDIATELY!
- CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
02/28/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*