Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04554
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PANEL NOT REPLACED PER OWNER |
|
04/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL PANEL COVER SCREWS 2. PANEL DIRECTORY TO BE CORRECT, NEAT AND LEGIBLE 3. INSTALL BLANKS IN MISSING BREAKER SPACES 4. PLANS SHOW BOTH EX. FAN ON TIME SWITCH 5. PANEL BUSS HAS BEEN DAMAGED FOR A FAULT, RECOMMEND REPLACEMENT OF PANEL 6. INSTALL ALL DEVICE COVERS 7. WIRING NOT PER PLAN? 8. SMOKE DETECTORS ARE TO BE 36" AWAY FROM VENTS |