Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/22/2008 | FRAMING | Partial Approval | IVRS - Inspection :* MOVING GARAGE STEM WALL CALL WHEN READY |
|
| 04/21/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WILL INSPECT GARAGE AFTER ENGINEERING FIX 2) FHA PLATE NEEDED BOTH SIDES OF INTERIOR BEARING WALL PER IRC 602.6.1 3) UFER CLAMP APPROVED INSTALLATION FOR BRAIDED UFER WIRE 4) NAIL PROTECT WIRES LEFT OF BACK PATIO DOOR TOP PLATE 5) FIREBLOCK SOFFIT IN LIVING ROOM 6) SEAL WEEP SCREED AT FRONT OF HOUSE TO BOTTOM PLATE 7) SEAL HOLES IN PAPER THROUGHOUT 8) NAIL OFF HOLDOWNS UNDER STAIRWAY 9) NAIL OFF SHEAR PANELS AT HOUSE/GARAGE WALL PER 303/ 508 DETAIL 10) DBL 2 X 12 HEADER NEEDED BETWEEN KITCHEN AND DINING 11) STOPPED INSPECTION AT MAIN FLOOR |
|
| 04/10/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |