Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04522
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. J-BOX FOR E-LIGHT SPLICES TO BE MADE ACCESSIBLE 2. L.B FITTING NOT TO BE BURIED IN WALL, MISSING LOCKNUT IN BOX 3. FINISH LOW VOLTAGE WIRING 4. USE SIDE K.O INTO FIRE ALARM SO FLEX WILL FIT IN WALL 5. J-BOX IN CEILING OVERFILLED. WIRE NUTS OVERFILLED. 6. INSTALL NAIL PLATE WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE |
|
12/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. WIRING NOT COMPLETE - DO NOT CALL BEFORE COMPLETED 2. INSTALL ALL MUD RINGS AND EXTENSIONS 3. CALL STATION TO BE RELOCATED 4. DEMO ALL ABANDONED WIRING & RACEWAYS TO SOURCE 5. SEAL UNUSED OPENINGS 6. RELOCATE T-STAT 7. INSTALL NAIL PLATES AS NEEDED (LESS THAN 1 1/4" FROM STUD FACE) 8. GROUND ALL METAL BOXES - SHEETMETAL/SELF TAP SCREWS NOT ALLOWED 9. EXTEND EMERGENCY LIGHT 10. SWITCHES/J-BOXES TO BE ACCESSIBLE 11. BOXES TO MOUNT WITH EXTERIOR BRACKET - NOT SCREWS ON INSIDE 12. MC TO BE SECURED WITHIN 12" OF TERMINATIONS |
|
12/10/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |