Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04522

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. J-BOX FOR E-LIGHT SPLICES TO BE MADE ACCESSIBLE
2. L.B FITTING NOT TO BE BURIED IN WALL, MISSING LOCKNUT IN BOX
3. FINISH LOW VOLTAGE WIRING
4. USE SIDE K.O INTO FIRE ALARM SO FLEX WILL FIT IN WALL
5. J-BOX IN CEILING OVERFILLED. WIRE NUTS OVERFILLED.
6. INSTALL NAIL PLATE WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE
12/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. WIRING NOT COMPLETE - DO NOT CALL BEFORE COMPLETED
2. INSTALL ALL MUD RINGS AND EXTENSIONS
3. CALL STATION TO BE RELOCATED
4. DEMO ALL ABANDONED WIRING & RACEWAYS TO SOURCE
5. SEAL UNUSED OPENINGS
6. RELOCATE T-STAT
7. INSTALL NAIL PLATES AS NEEDED (LESS THAN 1 1/4" FROM STUD FACE)
8. GROUND ALL METAL BOXES - SHEETMETAL/SELF TAP SCREWS NOT ALLOWED
9. EXTEND EMERGENCY LIGHT
10. SWITCHES/J-BOXES TO BE ACCESSIBLE
11. BOXES TO MOUNT WITH EXTERIOR BRACKET - NOT SCREWS ON INSIDE
12. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
12/10/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED