Inspection History: FRAMING

Date Description Inspector Results Comments
04/28/2008 FRAMING Approved IVRS - Inspection :*
04/25/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1, 2 AND 3 FROM PREVIOUS
04/22/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPAIR OVERNOTCH DOUBLE TOP PLATE KITCHEN WALL
2. FIRESTOP ARCHES THROUGHOUT
3. (2) AB'S PER SHEAR WALL
4. LOOSE REDHEADS THROUGHOUT
5. MISSING NAILS MECH ROOM LID
6. AC LINES AT TOP PLATE FIX A STRAP STRESSED
04/15/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO DWV TEST
2) MISSING PROTECTION PLATES ON ELECTRICAL CONDUCTORS THROUGHOUT
3) NEED TO SEAL AT WEEP FROM INSIDE HOUSE
4) NEED PROTECTION PLATES ON PLUMBING AT BATH TUB
5) STAPLE WIRE MESH ABOVE WINDOWS AND SEAL ALL CUT OUTS