Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04516
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTR. TO MAKE LAST MINUTE REPAIR ON VANDALIZED SERVICE GROUND, INSP. WILL MAKE COURTESY INSP. ON MONDAY CONTR. TO REPAIR ASAP |
|
03/28/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* RETURN INSP. 4 PM CONTR. REQUEST AFTER HRS. INSP. PAID $150.00 -- CK#61361 |
|
03/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - SEE NOTE #1 SHEET "E2" NEED REVISION OR LETTER FROM ARCH. TO ALLOW USE OF EXISTING WIRING ALSO, ADDRESS DELETION OF NEW PANEL - CK ALL EM LIGHTING - COVER ALL UNUSED OPENINGS IN BOXES, FIXTURES, ETC. |
|
03/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CK GROUNDING ON STRIP FIXTURES 2. MC CABLE TO SUPPORT TO STRUCTURE RETURN INSP. AFTER HRS. CONTR. REQUEST PAID $150.00 CK#61314 - OK GROUNDING STRIP FIXTURES - OK MC CABLE SUPPORT AT DRESSING ROOMS - OK ABOVE CEILING SALES FLOOR |
|
03/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - SUPPORT CONDUIT, FLEX, BOXES, SPEAKER CANS, WITH SEISMIC OR OTHER SUPPORTS, CONDUIT CONNECTORS DO NOT HAVE LOCKNUTS INSTALLED? |
|
02/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DRESSING ROOM ROUGH |
|
02/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - CANNOT BEND MC MORE THAN 7 TIMES DIA. - USE T-BAR HANGERS EQUIPPED WITH FOR SEISMIC GRID - OK PONY WALL AT ENTRANCE |
|
02/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OFFICES & RESTROOMS |
|
02/12/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* RESCHEDULE INSPECTION AFTER AIR IS CLEAR FROM PAINTING |
|
02/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT CONDUITS IN CEILING IN BOOKKEEPING AND MANAGER OFFICE |
|
02/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK TO ONE SIDE, SUBJECT TO OTHER INSPECTORS APPROVAL - LOOSE CONNECTORS, MISSING LOCKNUTS |
|
01/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DEMISING WALL IN BACK NEED TO SEE MAKEUP PRIOR TO CLOSING UP BOX |