Permit: T07CM04516

Parcel: 119180930


Addresses:

3754 S 16TH AV


Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04516

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
03/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTR. TO MAKE LAST MINUTE REPAIR ON VANDALIZED SERVICE GROUND, INSP. WILL MAKE COURTESY INSP. ON MONDAY CONTR. TO REPAIR ASAP
03/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
RETURN INSP. 4 PM
CONTR. REQUEST AFTER HRS. INSP. PAID $150.00 -- CK#61361
03/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SEE NOTE #1 SHEET "E2" NEED REVISION OR LETTER FROM ARCH. TO ALLOW USE OF EXISTING WIRING ALSO, ADDRESS DELETION OF NEW PANEL
- CK ALL EM LIGHTING
- COVER ALL UNUSED OPENINGS IN BOXES, FIXTURES, ETC.
03/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CK GROUNDING ON STRIP FIXTURES
2. MC CABLE TO SUPPORT TO STRUCTURE

RETURN INSP. AFTER HRS.
CONTR. REQUEST
PAID $150.00 CK#61314

- OK GROUNDING STRIP FIXTURES
- OK MC CABLE SUPPORT AT DRESSING ROOMS
- OK ABOVE CEILING SALES FLOOR
03/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SUPPORT CONDUIT, FLEX, BOXES, SPEAKER CANS, WITH SEISMIC OR OTHER SUPPORTS, CONDUIT CONNECTORS DO NOT HAVE LOCKNUTS INSTALLED?
02/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DRESSING ROOM ROUGH
02/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- CANNOT BEND MC MORE THAN 7 TIMES DIA.
- USE T-BAR HANGERS EQUIPPED WITH FOR SEISMIC GRID
- OK PONY WALL AT ENTRANCE
02/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OFFICES & RESTROOMS
02/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RESCHEDULE INSPECTION AFTER AIR IS CLEAR FROM PAINTING
02/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPORT CONDUITS IN CEILING IN BOOKKEEPING AND MANAGER OFFICE
02/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK TO ONE SIDE, SUBJECT TO OTHER INSPECTORS APPROVAL
- LOOSE CONNECTORS, MISSING LOCKNUTS
01/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DEMISING WALL IN BACK
NEED TO SEE MAKEUP PRIOR TO CLOSING UP BOX