Permit: T07CM04510

Parcel: 12008781A


Addresses:

702 W IRVINGTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/08/2019 MECHANICAL - ABOVE CEILING Approved
12/22/2014 MECHANICAL - ABOVE CEILING Partial Approval CHANGED FROM AP TO PA TO ALLOW FOR REINSPECTION PER REVISION
08/19/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
EXISTING AREA OK FOR CEILING TILES MECHANICAL ITEMS ONLY
08/13/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL ALL VAPOR BARRIERS ON DUCT WRAP
2. SEAL ALL JOINTS IN DUCT
3. SEAL ALL START COLLARS, SUPPLY AND RETURN
4. PROVIDE PROPER AMOUNT OF SCREWS IN STRAPS
PER S.M.A.C.N.A STANDARDS
07/31/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12" ROUND PIPE ABOVE CEILING
OK TO COVER MECHANICAL ONLY
NEW BUILDING ONLY

VERIFY BOOT TAPS AND SQUARE TO ROUNDS
ARE LINED OR INSULATE ON EXISTING BUILDING
07/28/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12" NO DUCT ABOVE CEILING NOT PROPERLY SUPPORTED
TO AVOID INSULATION COMPRESSION