Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2013 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 12/26/2013 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 12/10/2013 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
| 12/03/2013 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/03/2013 | ELECTRIC - TEMP POWER FOR TEST | Denied | PLAN CALLS FOR 200 AMP PANEL "HS" | |
| 10/22/2013 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/22/2013 | ELECTRIC - TEMP POWER FOR TEST | Denied | 1. NEUTRAL CONDUCTORS TO BE I.D. AS WHITE OR BLACK WITH WHITE ON LARGER THAN #6. WIRE WITH GREEN STRIP NOT TO BE USED AS NEUTRAL 2. NO PARALLEL GROUND PATHS ON SUPPLY SIDE OF MAIN DISC SW AT SERVICE 3. APPROVED PLAN TO MATCH FIELD INSTALL 4. FUSES & R-PINS NOT INSTALLED 5. BOND BUSHINGS IN GUTTER |