Permit: T07CM04509

Parcel: 11005535A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04509

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
07/17/2008 MECHANICAL - ABOVE CEILING Partial Approval ALL DUCTING ABOVE BUILDING INSTALLATION IS REQUIRED TO BE INSULATED WITH R-8

PLANS REQUIRE BUILDING R-30 INSTALLATION TO BE @ ROOF DECK NOT DOWN @ THE CEILING
07/15/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
NO ACCESS
07/11/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS REQUIRE LINED BOXES ON TOP OF RETURN AIR GRILLS
2. SUPPORT FLEX DUCTS EVERY 4' WITH NO DIPS OR SAGS MORE THAN 1 1/2" IN A 4' SPAN