Permit: T07CM04491

Parcel: 141313210

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM04491

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2008 EXT METAL CLIPS/EXT SHEATHING Approved
02/01/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) FRONT BEDROOM 7/SD3 SHEAR TRANSFER NOT DONE, CHECK SHINNERS AT VERTICAL JOINT
2) CHECK AT INTERMEDIATE #3 SHEAR TRANSFER NOT NAILED ADD SPACERS GAP IS TO LARGE, BLOCK TO PLATE THEN NAIL
01/30/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MORE BLOCKS 16A/SD3 16" ON CENTER
2) INTERIOR SHEARWALLS WITH BLOCKING 4/SD? PANELS BETWEEN TRUSSES NAIL TO DBL TOP PLATES. BLOCK BETWEEN WEBS NAIL VERTICAL SIDES
3) ADD WIND BRACE EAST SIDE 25' ON CENTER
4) #1, #3 SHEAR TRANSFER INTERIOR NOT NAILED
5) FRONT BEDROOM EXT. SHEAR TRANSFER NOT CONNECTED
6) TWO PIECES OF 7/SD3 CC PLY REAR GABLE TURNED OPPOSITE TRUSS CHORD BLOCKS NEEDED
7) NAIL 2 X 4 ATTACHED TO KNEE BRACES TO ROOF