Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUIT FOR LV CABLES ALSO, SCHED. 80 DEG. ABOVE GRADE 2. CABLES TO BE AT A DEPTH PER 300.5 3. CORD NOT ALLOWED FOR WIRING METHOD 4. TIGHTEN LOOSE FITTINGS 5. GROUND JUNCTION BOX 6. CONDUIT NOT LARGE ENOUGH FOR SPLICES 7. LABEL BREAKERS 8. PLEASE VERIFY PERMITS FOR NEW WIRING & PANEL IN BASEMENT |