Permit: T07CM04461

Parcel: 116190340


Addresses:

450 N GRANADA AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT CONDUIT FOR LV CABLES ALSO, SCHED. 80 DEG. ABOVE GRADE
2. CABLES TO BE AT A DEPTH PER 300.5
3. CORD NOT ALLOWED FOR WIRING METHOD
4. TIGHTEN LOOSE FITTINGS
5. GROUND JUNCTION BOX
6. CONDUIT NOT LARGE ENOUGH FOR SPLICES
7. LABEL BREAKERS
8. PLEASE VERIFY PERMITS FOR NEW WIRING & PANEL IN BASEMENT