Permit: T07CM04443

Parcel: 13705507B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOFFITS
04/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK STOCKROOM WALLS, HARD LIDS IN FITTING & BATHROOMS
04/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH & SOUTH FRONT WALLS ROUGH
03/31/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT CONDUIT WITHIN 3' OF TERMINATION PER NEC
2. MC CABLE MUST BE 1 1/4" MIN. BEHIND STUD FACE TO PROTECT FROM SCREWS. SUPPORT WITHIN 12" OF BOX OR TERMINATIONS, AND AT 6' INTERVALS, USE STRAPS
LISTED FOR MC SUPPORT, 1/2" CONDUIT STRAPS NOT APPROVED PER NEC
3. PROVIDE LETTER FROM ARCH. FOR APPROVAL
TO USE MC CABLE